Correct sizing
A module’s power rating in Wp reflects a laboratory value measured under defined test conditions. This standard was introduced to make module power ratings comparable. In real-world operation, these conditions are rarely met—actual output is usually lower. The table below shows the percentage of the maximum possible yield. The values are based on roof pitch and orientation—i.e., the deviation in degrees from the optimal south-facing direction (0°).
| Pitch |
0° (S) |
30° |
60° |
90° (E/W) |
120° |
150° |
180° (N) |
| 0° |
87 % |
87 % |
87 % |
87 % |
87 % |
87 % |
87 % |
| 10° |
93 % |
92 % |
90 % |
86 % |
83 % |
80 % |
79 % |
| 20° |
97 % |
96 % |
91 % |
85 % |
77 % |
71 % |
70 % |
| 30° |
100 % |
97 % |
91 % |
82 % |
72 % |
64 % |
61 % |
| 40° |
100 % |
97 % |
90 % |
79 % |
67 % |
56 % |
52 % |
| 50° |
98 % |
95 % |
87 % |
75 % |
61 % |
48 % |
43 % |
| 60° |
94 % |
91 % |
82 % |
70 % |
55 % |
41 % |
35 % |
| 70° |
88 % |
85 % |
76 % |
70 % |
49 % |
35 % |
28 % |
| 80° |
80 % |
77 % |
68 % |
56 % |
42 % |
29 % |
23 % |
| 90° |
69 % |
67 % |
60 % |
48 % |
35 % |
24 % |
18 % |
Again: these values represent the maximum possible yield, which is rarely achieved in real life—or only for short moments. You can safely subtract 10–20% from these values to determine a suitable inverter rating. However, since price jumps between the relevant power classes are usually not significant, choosing the next higher rating is often a perfectly good option.
Examples:
A 10 kWp system with a 30° roof pitch and a south-facing orientation has a maximum possible output of 100%. Since this is rarely reached, you can undersize the inverter by 10–20%, which would point to a unit with around 8–9 kW nominal power. An 8 kW inverter would be sufficient for most of the summer, but tends to be too small during the shoulder seasons. Since 9 kW models are uncommon, a 10 kW inverter is usually the best choice.
With an east–west orientation, a 10 kWp system at a 30° roof pitch achieves 82% maximum possible output. Again, since this is rarely reached, you can subtract around 10–20% and end up with an inverter nominal rating of about 6–7 kW. A 6 kW inverter would be sufficient for most of the summer, but tends to be too small in spring and autumn. Since 7 kW models are uncommon, an 8 kW inverter is recommended.
You’re welcome to contact us and we’ll take care of the system design for you.